Performance Data -
Models PPD1, PPD2, PPD3, PPDD

Maximum

Modulated Flow Selection Table

Inlet
0.10 Duct Ps
0.20 Duct Ps
0.30 Duct Ps
0.40 Duct Ps
Size
CFM
Throw, Ft.
NC
CFM
Throw, Ft.
NC
CFM
Throw, Ft.
NC
CFM
Throw, Ft.
NC

6
20
0-0-1
-
28
0-1-2
16
36
0-1-2
22
44
0-1-2
27
54
0-1-2
-
79
0-1-3
23
96
1-2-3
29
112
1-2-3
33
77
0-1-3
15
111
1-2-3
25
134
2-2-4
31
156
2-2-4
36
109
1-2-3
17
152
2-2-4
27
186
2-3-4
33
214
2-3-5
38

8
46
1-1-3
-
64
1-2-4
24
79
2-2-5
30
91
2-3-5
35
112
2-3-5
20
158
3-4-7
31
193
3-5-8
37
223
4-5-8
41
170
3-4-7
23
240
4-6-9
33
294
5-7-10
39
340
5-7-10
44
242
4-6-9
36
342
6-7-10
36
419
7-8-12
42
484
7-9-12
46

10
95
1-2-4
23
135
2-3-6
33
165
3-4-8
38
190
3-4-9
43
190
3-4-8
26
268
4-6-10
36
329
5-7-12
42
379
5-8-12
46
274
4-6-11
28
388
6-8-13
38
475
7-10-14
44
549
8-11-15
48
365
6-9-12
29
517
8-10-14
39
633
9-11-16
45
730
10-12-17
49

12
120
2-3-6
27
169
3-4-8
36
208
3-5-9
42
240
4-6-10
46
202
3-4-9
28
285
4-6-11
38
349
5-8-12
43
404
6-9-13
47
311
5-7-11
29
441
6-9-13
39
540
8-10-15
44
623
9-11-16
48
478
8-10-14
30
675
10-12-17
40
827
11-13-18
45
955
11-14-20
49

14
139
3-4-8
27
197
4-5-9
36
241
4-7-10
42
278
5-8-11
46
213
3-5-9
28
302
5-7-11
37
370
6-8-12
43
427
6-9-13
46
370
5-8-12
30
524
8-10-15
39
641
9-11-16
44
741
10-12-17
48
555
9-11-15
30
785
10-13-18
40
962
11-14-20
45
1111
12-15-21
49


Performance Notes:

  1. Performance data is presented for the Prodigy® diffuser at several modulated inner cone positions with constant duct static pressures of 0.10, 0.20, 0.30 and 0.40 inches w.g..
  2. Air flow is in cubic feet per minute, cfm.
  3. Throw is in feet at terminal velocities of 150, 100 and 50 fpm.
  4. Throw data is based on supply air and room air being at isothermal conditions.
  5. NC is based on 10 dB room absorption. Blanks indicated a value of less than 15.
  6. Tested in accordance with ASHRAE Standard 70-1991 “Method of testing for Rating the Performance of AIr Outlets and Inlets.”